The following table lists the characteristics and requirements for your hardware.
|
Physical characteristics
|
|
|
Weight
|
121 lbs (54.885 kg)
|
|
Rack units
|
6U
|
|
Height
|
10.32 in. (26.21 cm)
|
|
Width
|
17.53 in. (44.52 cm)
|
|
Depth (including cable management tray)
|
29 in. (73.66 cm)
|
|
Clearance dimensions
|
|
|
Front--cooling
|
All versions
|
6 in. (15.2 cm)
|
|
Rear--cooling
|
Two-post rack
|
12 in. (30.5 cm)
|
|
Four-post rack
|
12 in. (30.5 cm)
|
|
Front of chassis--maintenance
|
Two-post rack
|
25 in. (63.5 cm)
|
|
Four-post rack
|
25 in. (63.5 cm)
|
|
Rear of chassis--maintenance
|
Two-post rack
|
40 in. (102 cm)
|
|
Four-post rack
|
40 in. (102 cm)
|
|
Environmental requirements
|
|
|
Operating temperature maximum range
|
50 F to 104 F (10 C to 40 C)
|
|
Operating temperature recommended range
|
68 F to 77 F (20 C to 25 C)
|
|
Nonoperating temperature range
|
-4 F to 149 F (-20 C to 65 C)
|
|
Relative humidity
|
20 to 80% noncondensing
|
|
Acoustic level
|
54 dBA @ 23 C
|
|
Electrical requirements
|
|
|
Input voltage, V
|
100-240
|
|
Input current actual, A
|
10.63-5.19
|
|
Input power actual, W
|
938
|
|
Thermal dissipation, BTU/hr
|
3,201
|
|
Inrush current, A @ V
|
N/A
|