The following table lists the characteristics and requirements for your hardware.
|
Physical characteristics
|
|
|
Weight
|
Storage engine
|
105 lbs (47.7 kg)
|
|
DS14mk2 AT
|
77 lbs (35 kg)
|
|
Fully loaded in system cabinet
|
50.06 lbs (23 kg)
|
|
Rack units
|
Storage engine
|
6U
|
|
DS14mk2 AT
|
3U
|
|
Height
|
Storage engine
|
10.3 in. (26.2 cm)
|
|
DS14mk2 AT
|
5.25 in. (13.3 cm)
|
|
Width
|
Storage engine
|
17 in. (43.2 cm)
|
|
DS14mk2 AT
|
17.6 in. (44.8 cm)
|
|
Depth
|
Storage engine
|
22 in. (55.9 cm)
|
|
DS14mk2 AT
|
21.75 in. (55.2 cm)
|
|
Clearance dimensions
|
|
|
Front
|
Storage engine and DS14mk2 AT
|
25 in. (63.5 cm)
|
|
Rear--cooling
|
Storage engine and DS14mk2 AT
|
12 in. (30.5 cm)
|
|
Bezel
|
Storage engine and DS14mk2 AT
|
1.5 in. (3.8 cm)
|
|
Rear--maintenance
|
Storage engine and DS14mk2 AT
|
40 in. (101.6 cm)
|
|
Vertical rack space
|
Storage engine and DS14mk2 AT
|
10.5 in. (26.7 cm)
|
|
Vertical rack space between storage engine and disk shelf
|
Storage engine and DS14mk2 AT
|
1.5 in. (3.8 cm)
|
|
Environmental requirements
|
|
|
Operating temperature maximum range
|
Storage engine
|
50 F to 104 F (10 C to 40 C)
|
|
DS14mk2 AT
|
32 F to 104 F (10 C to 40 C)
|
|
Operating temperature recommended range
|
Storage engine and DS14mk2 AT
|
68 F to 77 F (20 C to 25 C)
|
|
Nonoperating temperature range
|
Storage engine and DS14mk2 AT
|
-4 F to 149 F (-40 C to 65 C)
|
|
Relative humidity
|
Storage engine
|
10 to 90% noncondensing
|
|
DS14mk2 AT
|
5 to 90% noncondensing
|
|
Acoustic level
|
Storage engine
|
49.5 dBA @ 23 C
|
|
DS14mk2 AT
|
48.7 dBA at 25 C 5.64 bels at 25 C
|
|
Electrical requirements
|
|
|
Input voltage, V
|
Storage engine
|
100-240
|
|
DS14mk2 AT
|
100-127/200-240
|
|
Input current actual, A
|
Storage engine
|
3.8-1.95
|
|
DS14mk2 AT
|
3.95/1.9
|
|
Input power actual, W
|
Storage engine
|
330
|
|
DS14mk2 AT
|
356
|
|
Thermal dissipation, BTU/hr
|
Storage engine
|
1,126
|
|
DS14mk2 AT
|
1,215
|
|
Inrush current, A @ V
|
Storage engine
|
30 @ 264
|
|
DS14mk2 AT
|
20 @ 220
|