The following table lists the characteristics and requirements for your hardware.
|
Physical characteristics
|
|
|
Weight
|
Loaded
|
Up to 1,110 lbs (505.5 kg)
|
|
Empty
|
312.4 lbs (142 kg)
|
|
Height
|
Cabinet
|
73 in. (185.4 cm)
|
|
Crate
|
79 in. (200.7 cm)
|
|
Width
|
Cabinet
|
24 in. (61.0 cm)
|
|
Crate
|
42 in. (106.7 cm)
|
|
Depth
|
Cabinet
|
36 in. (91.4 cm)
|
|
Crate
|
44.6 in. (113.3 cm)
|
|
Clearance dimensions
|
|
|
Front
|
25 in. (63.5 cm)
|
|
Rear
|
25 in. (63.5 cm)
|
|
Environmental requirements
|
|
|
Operating temperature maximum range
|
32 F to 104 F (0 C to 40 C)
|
|
Operating temperature recommended range
|
68 F to 77 F (20 C to 25 C)
|
|
Nonoperating temperature range
|
-40 F to 149 F (-40 C to 65 C)
|
|
Relative humidity
|
10 to 90% noncondensing
|
|
Electrical requirements
|
|
|
Input voltage, V
|
20A PDU
|
200-240
|
|
30A PDU
|
200-240
|
|
Input current actual, A
|
20A PDU
|
15.3
|
|
30A PDU
|
17.3
|
|
Input power actual, W
|
20A PDU
|
2,600
|
|
30A PDU
|
3,000
|
|
Thermal dissipation, BTU/hr
|
20A PDU
|
8,874
|
|
30A PDU
|
10,239
|
|
Outlet requirements
|
|
|
Plug type
|
2 x NEMA L6-30 North America
|
30A rated service
|
|
24A derated service (rms)
|
|
2 x IEC309-32 International
|
30A rated service
|
|
24A derated service (rms)
|
|
Note For complete power redundancy, the power distribution units (PDUs) must be connected to two separate AC circuits.
|