The following table lists the characteristics and requirements for your hardware.
|
Physical characteristics
|
|
|
Weight
|
Loaded
|
Up to 1,500 lbs (Up to 680 kg)
|
|
Empty
|
275 lbs (124.7 kg)
|
|
Height
|
Cabinet
|
78.7 in. (200 cm)
|
|
Crate
|
85.8 in. (218 cm)
|
|
Width
|
Cabinet
|
23.6 in. (60 cm)
|
|
Crate
|
29.8 in. (75.7 cm)
|
|
Depth
|
Cabinet
|
37.4 in. (95 cm)
|
|
Crate
|
48 in. (121.9 cm)
|
|
Clearance dimensions
|
|
|
Front
|
30 in. (76.3 cm)
|
|
Rear
|
30 in. (76.3 cm)
|
|
Top
|
12 in. (30 cm)
|
|
Environmental requirements
|
|
|
Operating temperature maximum range
|
32 F to 104 F (0 C to 40 C)
|
|
Operating temperature recommended range
|
68 F to 77 F (20 C to 25 C)
|
|
Nonoperating temperature range
|
-40 F to 149 F (-40 C to 65 C)
|
|
Relative humidity
|
10 to 90% noncondensing
|
|
Electrical requirements
|
|
|
Note The system cabinet offers two PDU options: you can order the cabinet with either two 30A PDUs or four 20A PDUs. The 20A PDU is derated at 16A, and the 30A PDU is derated at 24A. The following values refer to fully configured cabinets, unless specified otherwise.
|
|
Input voltage, V
|
20A PDU
|
200-240
|
|
30A PDU
|
200-240
|
|
Input current actual, A
|
20A PDU
|
11.5 per PDU*
|
|
30A PDU
|
25.2 per PDU
|
|
Input power actual, W
|
20A PDU
|
2,150 total
|
|
30A PDU
|
4,957 total
|
|
Thermal dissipation, BTU/hr
|
20A PDU
|
7,338 total
|
|
30A PDU
|
16,918 total
|
|
* Because there are two PDUs per side instead of one, the capacity is double this amount, although the PDUs must be connected to separate 20A branch circuits.
For details, see your System Cabinet Guide.
|
|
Outlet requirements
|
|
|
Plug type for 20A PDU
|
4 x NEMA L6-20 North America
|
4 x 20A rated service
|
|
4 x 16A derated service (rms)
|
|
International 4 x IEC309-20
|
4 x 20A rated service
|
|
4 x 16A derated service (rms)
|
|
Australia 4 x AS/NZS3123-20
|
4 x 20A rated service
|
|
4 x 16A derated service (rms)
|
|
Plug type for 30A PDU
|
NEMA L6-30 North America
|
30A rated service
|
|
24A derated service (rms)
|
|
IEC309-32 International
|
30A rated service
|
|
24A derated service (rms)
|
|
Note For complete power redundancy, the power distribution units (PDUs) must be connected to four separate AC circuits for the 20A PDU and two separate AC circuits for the 30A PDU.
|