Library Table of Contents Index Previous Page (Alt-p) Next Page (Alt-n) Comments

FAS270 systems and GF270c gateways

FAS270 and GF270c characteristics  Top

The following table lists the characteristics and requirements for your hardware.

Physical characteristics

 

Weight

With disk drives

77 lbs (35 kg)

Empty

50.6 lbs (23 kg)

Rack units

3U

Height

5.25 in. (13.3 cm)

Width

17.6 in. (44.8 cm)

Depth

20 in. (50.9 cm)

Clearance dimensions

 

Front--cooling

All versions

6 in. (15.3 cm)

Rear--cooling

Two-post rack

12 in. (30.5cm)

Four-post rack

12 in. (30.5 cm)

Front--maintenance

Two-post rack

25 in. (63.5 cm)

Four-post rack

25 in. (63.5 cm)

Rear--maintenance

Two-post rack

12 in. (30.5 cm)

Four-post rack

12 in. (30.5 cm)

Environmental requirements

 

Operating temperature
maximum range

32 F to 104 F
(10 C to 40 C)

Operating temperature
recommended range

68 F to 77 F
(20 C to 25 C)

Nonoperating temperature range

-40 F to 149 F
(-40 C to 65 C)

Relative humidity

10 to 90% noncondensing

Acoustic level

48.7 dBA@ 23 C

5.64 bels @ 23 C

Electrical requirements

 

Input voltage, V

100-127/200-240

Input current actual, A

3.95/1.9

Input power actual, W

356

Thermal dissipation, BTU/hr

1,215

Inrush Current, A @ V

20 @ 220

Library Table of Contents Index Previous Page (Alt-p) Next Page (Alt-n) Comments