To cable the Channel A connections of your cluster, follow these steps.
| Step | Action |
|---|---|
| 1 |
For an F630 filerConnect the filer to disk shelf 0 by
|
For an F740 and an F760 filerConnect the filer to disk shelf 0 by
| |
| 2 | Terminate the loop by putting a terminator on the LRC Output/Terminator connector. |
| 3 | Repeat Steps 1 through 3 for the partner filer. |
For an F630 filerThe cabling for the minimum configuration should be as shown in the following figure.
| |
For an F740 and an F760 filerThe cabling for the minimum configuration should be as shown in the following figure.
| |
| 4 | Proceed to "How to terminate the Channel B loops in a minimum configuration." |
To terminate the Channel B connections of the disk shelves in your minimum cluster configuration, follow these steps.
| Step | Action |
|---|---|
| 1 |
Place a terminator on the LRC Output/Terminator connector of the Channel B LRC card.
Caution: Do NOT complete the Channel B loop to the partner filer. If you complete the Channel B loop to the partner filer and reboot, the filers try to take ownership of both sets of disks and cause permanent damage to your file systems. |
| 2 | Repeat Step 2 for the partner filer. (The Channel A cabling that you did previously is also shown.) |
For an F630 filerThe result is as shown in the following figure.
| |
For an F740 and an F760 filerThe result is as shown in the following figure.
| |
| 3 | Proceed to "How to connect the filers in a minimum configuration." |
To connect the filers, follow these steps.