Power requirements

Inrush current and voltage requirements

What inrush
current is  Top

Inrush current is the measured peak of current from your AC source when you switch on the power supply at the peak of the input voltage. When you test
DC-to-DC power supplies, the inrush current is always the same.

List of inrush current  Top

The following table lists the inrush current and input voltage requirements with power applied to the disk shelf and storage appliances.

Hardware

Input voltage

Inrush current

FAS900 series appliance

264V AC

30A

F87 filer

240V AC

120V AC

66A

51A

F85 filer

220V AC

115V AC

70A

35A

F800 series filer, C6100/C3100 NetCache appliance

220V AC

110V AC

50A

40A

-40 DC to -70V DC

No greater than 25A under any condition

C2100 NetCache appliance

220V AC

115V AC

30A

25A

C1200 NetCache appliance

180-264V AC
90-140V AC

50A (max.)

F700 series filer/C700 series NetCache appliance

220V AC

115V AC

50A

40A

-40 DC to -70V DC

No greater than 25A under any condition

R100 system

220V AC

30A

R150 system

220V AC

60A

DS14 disk shelf

220V AC

40A

SDS12 disk shelf

220V AC

115V AC

40A

20A

FC9 disk shelf

220V AC

120V AC

30A

22A

-60V DC to -40V DC

Note
The DC power can operate from a -48V or +48V DC source.

No greater than 20A under any condition

FC7 and FC8 disk shelves

220V AC
115V AC

30A
22A

Library Table of Contents Index Previous Next Comments