Replacing a power supply in a GF270c consists of the following procedures:
When replacing the power supply in your gateway, observe the following rules:
Caution
Your gateway can run with one power supply for a maximum of two minutes. The airflow through your gateway is degraded when only one power supply is present and operating. Therefore, if the power supplies are not replaced within two minutes of each other, the system halts and no data is accessible.
Caution
A power load board is installed in the front of your GF270c to stabilize the power supplies. Do not remove the power load board from your gateway.
To remove a power supply, complete the following steps.
To install a power supply, complete the following steps.
Caution
Do not use excessive force when sliding the power supply into your gateway. You can damage the connector.
| 1 |
Put on the antistatic wrist strap and grounding leash. |
|
| 2 |
Slide the power supply into the power supply bay until you hear the power supply connect with the connector inside your gateway chassis. |
|
| 3 |
Raise the handle while pressing the cam mechanism levers toward each other, and push the power supply handle into place. The following figure shows how to raise the handle into place.
|
|
| 4 |
Plug the power cord into the power receptacle and fasten it with the clamp. |
|
| 5 |
Plug the other end of the power cord into a grounded AC power source. |
|
| 6 |
Turn on the power switch and confirm proper operation by checking the power supply LEDs. See Monitoring the power supply. |
|
| 7 |
After turning on your system, run diagnostics. See the Diagnostics Guide for more information. |
|